Peak Shaving and the Global Adjustment: Class A vs Class B for Ontario Businesses


Every Ontario business pays the Global Adjustment (GA). Class B pays it per kWh, so solar cuts it directly. Class A pays by its share of Ontario's five highest-demand hours each year, so a battery run on those hours can cut a full year of GA. Class A starts at an average peak of 500 kW for manufacturers and greenhouses and 1 MW for everyone else.
For many Ontario businesses the GA is a bigger cost than the energy itself. How you are billed for it decides whether solar, a battery or a change in operations saves the most.
| Class B | Class A (Industrial Conservation Initiative) | |
|---|---|---|
| How GA is billed | Per kWh, at a monthly rate the IESO publishes | Your share of Ontario's top five peak hours (your peak demand factor) |
| Timing | Each month's use | Peaks measured May 1 – April 30; that share is billed July 1 – June 30 |
| What lowers it | Using fewer grid kWh, at any time | Drawing less from the grid in those five hours |
| Who | Most businesses | Eligible larger users who opt in, or are automatically in above 5 MW |
Small businesses on the Regulated Price Plan pay the GA inside their time-of-use or tiered prices rather than as a separate line.
The opt-in or opt-out decision is due by June 15 each year. Separate buildings cannot be combined to reach a threshold.
For Class B, every kWh your panels produce and you use on site avoids the energy price and the GA riding on it, so solar has a direct, all-year effect. For Class A, solar helps only if it is producing during the five peak hours. Those usually fall on hot summer weekdays, late in the afternoon or early evening, when solar output is already declining, so solar alone is an unreliable peak tool.
For Class A, a battery is the main peak-shaving tool. Charged ahead of time and discharged during forecast peak hours, it lowers your draw in exactly the hours that set the next year's GA share. Two cautions: you must predict the peaks (the IESO publishes a peak tracker, and forecasting services exist), and missing even one peak costs you. For Class B, a battery does little for the GA, since it shifts kWh rather than reducing them; its value there is demand charges and backup. Storage qualifies for the 30% Clean Technology ITC for taxable corporations.
| Your situation | Usually the best first step |
|---|---|
| Class B, daytime operations | Solar sized to daytime load |
| Class B, large HVAC load | Peak Performance, alongside solar |
| Eligible for Class A, flexible operations | Compare Class A vs B with your utility's analysis; curtail on peak days |
| Class A, operations that cannot pause | Battery sized to cover your peak window |
Your utility sends Class A candidates their peak demand factor and a Class A vs Class B comparison each spring. Start there. See also how business electricity bills work and commercial solar cost and payback.
The part of Ontario's electricity cost that covers contracted and regulated generation, infrastructure and conservation programs, on top of the market price.
Your average monthly peak demand over the base period must exceed 1 MW, or 500 kW for manufacturers and greenhouses. Your utility tells eligible customers by May 31.
For Class B, yes, on every kWh you no longer buy. For Class A, only to the extent it produces during the five peak hours.
Verified October 15, 2026. Rules and rates change; confirm eligibility and your peak demand factor with your utility. General information, not financial advice.